Legislation
Emissions Limits
- Emission limit values after the 1. BImSchV
- Emissions limits for biomass firing plants after TA Luft (Clean Air Legislation)
- Overview of the regulations after BImSchG and the emission limit values for untreated wood
- Overview of the regulations after BImSchG and the emission limit values for straw
Emission limit values after 1. BImSchV | |||||
Fuel | Nominal heat achievement in kW | Oxygen reference value in % | Emission limit values | ||
| Dust a | CO a | Waste gas plume | ||
| in g/Nm3 | in g/Nm3 | Grey tone | ||
Natural wood | < 50 | 13 | 0,15 | 4,0 | more bright 1 |
| 50 - 150 |
|
| 2,0 |
|
| 150 - 500 |
|
| 1,0 |
|
| > 500 |
|
| 0,5 |
|
|
|
|
|
|
|
Wood, painted, paints, | b 100 | 13 | 0,15 | 0,8 | more bright 1 |
coated, plywood, | 100 - 500 |
|
| 0,5 |
|
Chip boards, fiber boards | > 500 |
|
| 0,3 |
|
as well as their remainder without |
|
|
|
|
|
halogeneous-organic |
|
|
|
|
|
Coatings and |
|
|
|
|
|
Wood preservatives |
|
|
|
|
|
|
|
|
|
|
|
Straw or the like | c < 50 | 13 | 0,15 | 4,0 | more bright 1 |
vegetable materials | 50 - 100 |
|
| 2,0 |
|
|
|
|
|
| |
Abbreviations:
BImSchG: Federal Emission Control Law
1. BImSchV: First regulation for the execution of the BImSchG (regulations for small firing plants)
CO: Carbon monoxide
Nm3: Standard cubic meter, exhaust gas at standard temperature and pressure with 0° C and 1013 mbar with indicated oxygen reference value
Footnotes:
a Dust and CO limit only during nominal heat output> 15 kW
b Not applied during a nominal heat output< 50 kW
c Not applied during a nominal heat output < 15 kW
Emission limits for biomass firing plants after TA Luft a | |||
|
| Emission limit value | Note |
Oxygen reference value | in Vol.-% | 11 |
|
|
|
|
|
Dust | in g/Nm³ | 0,15 | FWL < 5 MW |
| in mg/Nm³ | 50 | FWL >= 5 MW |
|
|
|
|
Carbon monoxide (CO) | in g/Nm³ | 0,25 | with FWL < 2.5 MW only with nominal load |
|
|
|
|
Organic materials (entire CC) | in mg/Nm³ | 50 |
|
|
|
|
|
Nitrogen oxides indicated as | in g/Nm³ | 0,3 | stat. WS > 20 MW and zirk. WS |
(NO2 ) |
| 0,4 | other plants (natural wood, straw) |
|
| 0,5 | other plants |
|
|
|
|
Sulfur dioxides (SO2) | in g/Nm³ | 2 |
|
Abbreviation:
TA Luft: Technical guidance for the keeping clean of air
stat. WS: stationary fluidized bed
zirk. WS: circulating fluidized bed
Nm3: Standard cubic meter, exhaust gas at standard temperature and pressure with 0° C and 1013 mbar with indicated oxygen reference value
FWL: Firing thermal output
Footnote:
a with consideration of the Dynamisierungsklauseln of the land committee for emission control (LAI)
Overview of the regulations after BImSchG and the emission limit values for untreated wood
Equipment performance |
| Licensing | Relevant | Oxygen reference | Emission limit values |
|
|
|
|
|
| procedures | Regulation | value | Dust | CO | Ges.-C | NOX | SO2 |
|
|
|
| in Vol.-% | in g/Nm³ |
|
|
|
|
FWL < 1 MW |
| not | 1. BImSchV | 13 |
|
|
|
|
|
| NWL <= 50 kW | subject |
|
| 0,15 | 4 | - | - | - |
| NWL 50 - 150 kW | to |
|
| 0,15 | 2 | - | - | - |
| NWL 150 - 500 kW | approval |
|
| 0,15 | 1 | - | - | - |
| NWL > 500 kW |
|
|
| 0,15 | 0,5 | - | - | - |
FWL 1 - 50 MW |
| vereinf. Verf. | TA Luft | 11 |
|
|
|
|
|
| FWL < 5 MW | (§ 19 BImSchG) |
|
| 0,15 | 0,25 | 0,05 | 0,4 | 2 |
| FWL >= 5 MW |
|
|
| 0,05 | 0,25 | 0,05 | 0,4 | 2 |
FWL >= 50 MW |
| förml. Verf. | 13.BImSchV | in accordance with 13. BImSchV (large firing regulation; usually not relevantly for biomass) |
|
|
|
|
|
|
| (§ 10 BImSchG) |
|
|
|
|
|
|
|
Abbreviation:
FWL: Firing thermal output, NWL: Nominal heat output
Overview of the regulations after BImSchG and the emission limit values for straw
Equipment performance |
| Licensing | Relevant | Oxygen reference | Emission limit values | ||||
|
| procedures | Regulation | value | Dust | CO | Ges.-C | NOX | SO2 |
|
|
|
| in Vol.-% | in g/Nm³ | ||||
FWL < 1 MW |
| not | 1. BImSchV | 13 |
|
|
|
|
|
| NWL <= 50 kW | subject |
|
| 0,15 | 4 | - | - | - |
| NWL 50 - 150 kW | to |
|
| 0,15 | 2 | - | - | - |
| NWL 150 - 500 kW | approval |
|
| 0,15 | 1 | - | - | - |
| NWL > 500 kW |
|
|
| 0,15 | 0,5 | - | - | - |
FWL 1 - 50 MW |
| vereinf. Verf. | TA Luft | 11 |
|
|
|
|
|
| FWL < 5 MW | (§ 19 BImSchG) |
|
| 0,15 | 0,25 | 0,05 | 0,4 | 2 |
| FWL >= 5 MW |
|
|
| 0,05 | 0,25 | 0,05 | 0,4 | 2 |
FWL >= 50 MW |
| förml. Verf. | 13.BImSchV | in accordance with 13. BImSchV (large firingregulation; usually not relevantly for biomass) | |||||
|
| (§ 10 BImSchG) |
|
|
|
|
|
|
|
Abbreviation:
FWL: Firing thermal output, NWL: Nominal heat output
Footnote:
a 15 not applicable during a nominal heat output < kW
Source:
Fichtner GmbH & Co. KG
Projektbereich Erneuerbare Energien (Project Area Renewable Energies)
Sarweystraße 3
70191 Stuttgart
Germany